R1-120A-I

Multiloop controller with 6 0/4-20 mA input channels

The R family includes a series of multiloop controllers well suited for all applications that require control of a large number of temperatures; all controllers can be mounted on a DIN rail and can be linked to a local operator panel (F1-10).
Different models are available for reading Pt100, thermocouples or linear signals (V/mA); for each loop it is possible to configure control type (heat, cool, heat/cool, ..), output type (on/off, time proportional, valve, ..) and alarm strategy or to run a auto-tuning procedure; furthemore it is possible to limit the energy conumption during start-up by programming a proper sequence of activation of PID loops.
R2 models have differential isolated channels that gives another substantial improovement to the features of these devices , expecially in noisy industrial environments.
A RS422/485 serial interface with Modbus (ASCII or RTU) protocol allows link of many controllers to the same master unit (PC, PLC or operator panel). 

Multiloop temperature controller for DIN rail mounting; 6 analog inputs for 0/4-20 mA; accurate readings without need of calibration; up to 6 PID loops; heat, cool or heat/cool control with various output types: on/off, time proportional, analog (with addition of C1-10 external module) or for motorized valve control (open/close); PID autotuning algorithm; programmable activation sequence to limit the energy consumption during start-up; dedicated interface for connection with a local operator panel (F1-10); RS422/485 serial interface with Modbus (ASCII or RTU) protocol; a common supervision of many controllers can be provided by any commercial SCADA software with modbus libraries or by HMI touch screen operator panels.

General specifications
Power supply: • From 9 to 36V DC, 100mA @24V DC (without F1-10), 170mA (with)
Power supply protections: • Against surge, voltage peaks and polarity inversion
Operating environment: • Temperature: from 0 to +70°C, RH: from 25 to 85% non condensing 
Operating atmosphere: • Without corrosive gas
Storage temperatur: • From -20 to +80°C (without ice)
Electromagnetic compatibility: • Radio frequency emissions: EN55011 group 1 class A
• Conducted emissions: EN55011 group 1 class A
• Radio frequency immunity: ENV50140 10V/m AM from 80 to 100MHz
• Conducted immunity: ENV50141 10V/m AM from 0.15 to 80MHz
IP grade: • Connectors: IP20, enclosure: IP20
Isolation: • Between analog inputs and digital inputs/outputs: 500V
• Between analog inputs and power supply section: 500V
• Between analog inputs and RS422/485 section: 1000V
• Between digital inputs/outputs and RS422/485 section: 1500V
• Between power supply and RS422/485 section: 1500V
LED indication: • Power on, self-test, digital inputs and outputs, serial Rx and Tx
Mounting: • DIN EN50022 rail
Dimensions: • 175 (L) x 120 (H) x 65(D) mm
Weight: • 450g
Ordering code: • R1-120A-I
Analog input specifications
Sensor type: • 6 Current sensors (from 0 to 20mA)
Analog/digital conversion: • Double ramp, 16 bit resolution
Current allowed: • From 0 to 250mA
Overall accuracy: •±10µA
Acquisition rate: • 1s (all six channels)
Input impedance: • 246 Ohm
Cold junction compensation: • 
Digital inputs specifications
Input type: • 2 Inputs, opto-isolated, common positive (power supply voltage)
Voltage levels: • Active state from: 15 to 36V, non active from: 0 to 4V
Current sinked: • 10mA @24V
Detectable pulse duration: • Not less than 500ms
Digital outputs specifications
Output type: • 12 Outputs PNP transistor open collector, pull down resistor: 22kOhm to ground
Output voltage when active: • The voltage supply
Maximum load current: • 100mA each output
Protections: • Suppression diode, overvoltages and short circuit
Communication interface specifications
Communication interface: • EIA RS485 or RS422 (selectable by dip-switch)
Communication speed: • 9600 or 19200 baud (selectable by dip-switch)
Communication protocol: • Modbus ASCII or Modbus RTU (selectable by dip-switch)
Device address: • From 1 to 63 (selectable by dip-switch)
485/422 Lines protections: • Agains surge, short circuits and voltage peaks
Pull-up and pull-down resistors: • 10kOhm
Functional specifications
Watch-dog: • Hardware
RAM data retention: • One hour max.
Read software filter: • Movig average, 8 samples depth (individully selectable for each channel)
Set-points: • Two, runtime selectable by using one of other channels
Set-point options: • Can be the temperature read from one of other channels
• Hold-back and soft start
• Set-point ramp, user configurable
Regulation strategies: • Heat, cool, heat/cool, with start order
Regulation algorithm: • Advanced PID, with cycle time selectable from 1 to 240s
Autotuning: • Yes
Outputs: • For SSR, with ramp and output limits user configurable
• For relays, with working cycles use configurable
• For motorized valves without potentiometric feedback
Alarms: • Band type and minimum/maximum type alarms, with time activation filter