DL-485MBP/6-PO-SMA
The systems DL-485MBP connect a MODbus-Plus interface to fiber optics field bus network. Point to Point, HCS fiber optic, SMA connector.
The ruggedness to electrical and magnetic interferences, the potential separation of transmitter and receiver as well as ranges up to 40km between two fiber optic systems are important performance features of the transmission with POF, HCS and multimode or singlemode fiber optics. LEDs and potential free contacts of a differential relay signalize defective states.
Apart from ST and SC as optical connection types, E2000 is also available. All systems feature communication with two fibers or a single fiber by BIDI technology with SC connection.
This system is now also available with the fiber optic monitoring technology FiberView.
The systems DL-485MBP connect field bus networks to a Modbus-Plus interface via fiber optics. This innovative system allows creating optical bus, star and tree structures as well as optically-electrically mixed structures.
The ruggedness to electrical and magnetic interferences, the potential separation of transmitter and receiver as well as ranges up to 40km between two fiber optic systems are important performance features of the transmission with POF, HCS and multimode or singlemode fiber optics. LEDs and potential free contacts of a differential relay signalize defective states.
Apart from ST and SC as optical connection types, E2000 is also available. All systems feature communication with two fibers or a single fiber by BIDI technology with SC connection.
This system is now also available with the fiber optic monitoring technology FiberView.
| FO connector: | • SMA |
| Fiber: | • HCS 200/230 μm |
| Optical budget: | • 15 dB |
| FO range: | • 120 m (10 dB/km) |
| Wavelength: | • 650 nm |
| Data rate max.: | • 1 MBit/s |
| Transmission type: | • Half-duplex |
| Signal delay: |
• Modbus Plus Interface ⇔ Fiber Optic: < 400ns / Tx ⇔ Rx : 500ns • MBPR : MODBUS Plus Interface ⇔ Fiber Optic : < 1μs |
| Terminating resistor: | • According to MODBUS Plus specifications: no terminating resistors in device |
| Cable length electr.: | • 50 m |
| Connecting plug: | • 9 pole Sub-D female and 6 pole terminal |
| Status - LEDs: | • Power supply (green) / Data (yellow) / Status (red) |
| Operating voltage: | • 12-30 VDC, other voltages on request |
| Power consumption: | • 5 Watts, 200 mA (24V) |
| Potential separation: | • 500 VDC (24 VDC ⇒ Modbus Plus Interface) |
| Operating temperature: |
• -40°C - +70°C (Multimode and Singlemode with ST or SC) • -20°C - +55°C (all others) |
| Storage temperature: | • -40°C - +85°C |
| Failure relay: | • 25VDC (1A) / 60VDC (0,3A) |
| EMC: | • EN61000-6-2 / EN55022 +A1 + A2 Class B |
| Weight: | • 500 g |
| Dimensions H x W x D: | • H: 115mm W: 61mm D: 113mm |
| Housing: | • Stainless steel, powder coated |
| Option: | • FiberView |
| Order number: | 01000 6402 |
• Industrial Modbus field bus network