DL-485PB/6-PO-SMA
The systems DL-485PB connect Profibus field bus networks via fiber optics. Point to Point, HCS fiber optic, SMA connector.
The ruggedness to electrical and magnetic interferences, the potential separation of transmitter and receiver as well as ranges up to 40km between two fiber optic systems are important performance features of the transmission with POF, HCS and multimode or singlemode fiber optics. LEDs and potential free contacts of a differential relay signalize defective states.
Apart from ST and SC as optical connection types, E2000 is also available. All systems feature communication with two fibers or a single fiber by BIDI technology with SC connection.
This system is now also available with the fiber optic monitoring technology FiberView.
The systems DL-485PB connect Profibus and field bus networks via fiber optics. This innovative system allows creating optical bus, star and tree structures as well as optically-electrically mixed structures.
The ruggedness to electrical and magnetic interferences, the potential separation of transmitter and receiver as well as ranges up to 40km between two fiber optic systems are important performance features of the transmission with POF, HCS and multimode or singlemode fiber optics. LEDs and potential free contacts of a differential relay signalize defective states.
Apart from ST and SC as optical connection types, E2000 is also available. All systems feature communication with two fibers or a single fiber by BIDI technology with SC connection.
This system is now also available with the fiber optic monitoring technology FiberView.
| FO Connector: | • SMA |
| Fiber: | • HCS 200/230 μm |
| Optical budget: | • 15 dB |
| FO range: | • 120 m (10 dB/km) |
| Wavelength: | • 650 nm |
| Data rate max.: | • 12MBit/s |
| Transmission type: | • Half-duplex |
| Signal delay: | • RS485 ⇔ Fiber Optic : < 3 TBit / Tx ⇔ Rx : 11 TBit |
| Termination resistor: | • Switchable: none or wave impedance (Rw + Rpd + Rpu) |
| Cable length electr.: | • 1.200m (9,6 – 187,5KBit/s), 400m (500KBit/s), 200m (1.5MBit/s), 100m (3MBit/s - 12MBit/s) |
| Connecting plug: | • 9 pole Sub-D female and 6 pole terminal |
| Status-LEDs |
• Power supply (green) / Failure (red) / Data receive (green) / Status (red)/ • FiberView (red, yellow, green) |
| Operating voltage: | • 12-30 VDC, other voltages on request |
| Power consumption: | • 5 Watts, 200 mA (24V) |
| Potential separation: | • 500 VDC (24 VDC ⇒ Profibus RS485) |
| Operating temperature: |
• -40°C - +70°C (Multimode and Singlemode with ST or SC) • -20°C - +55°C (all others) |
| Storage temperature: | • -40°C - +85°C |
| EMC: | • EN61000-6-2 / EN55022 +A1 + A2 Class B |
| Failure relay: | • 25VDC (1A) / 60VDC (0,3A) |
| Weight: | • 500 g |
| Dimensions HxWxD: | • H: 115mm W: 61mm D: 113mm |
| Housing: | • Stainless steel, powder coated |
| Options: | • FiberView |
| Order number | 01000 6202 |