DL-485/6-PO-SMA
The fiber optic systems DL485 connect applications with a RS485 interface via POF fiber optics with SMA connector.
The fiber optic systems DL-485 connect field bus systems with RS485 interfaces. The optical networking offers safe data transmission and it is suitable for MODBUS, MODNET-1/SFB, BITBUS, SAIA-S-BUS and many other manufacturer specific systems.
The fiber optic systems DL-485 connect field bus systems with RS485 interfaces. The optical networking offers safe data transmission and it is suitable for MODBUS, MODNET-1/SFB, BITBUS, SAIA-S-BUS and many other manufacturer specific systems.
This innovative system allows creating optical bus, star or tree structures as well as electrically-optically mixed structures.
The ruggedness to electrical and magnetic interferences, the potential separation of transmitter and receiver as well as ranges up to 40km between two fiber optic systems are important performance features of the transmission with POF, HCS and multimode or singlemode fiber optics. LEDs and potential free contacts of a differential relay signalize defective states.
Apart from ST, SC, SC-BIDI and SMA as optical connection types, E2000 is also available.
This system is now also available with the fiber optic monitoring technology FiberView.
| Fiber optic conector: | • |
| Fiber: | • |
| Optical budget: | • 12dB |
| FO range: | • |
| Wavelength: | • |
| Data rate max.: | • 1,5MBit/s (divided by the number of fibre-segments) |
| Transmission type: | • Full duplex, half duplex only with DL-422/2x |
| Operation type: | • DTE or DCE switchable with DIP-switch |
| Terminating resistor: | • switchable termination: open, Pull-Up (Rp) or characteristic impedance (Rw) |
| Cable length electr.: | • 50m |
| Connecting plug: | • 9 pole Sub-D female and 6 pole terminal |
| Status LEDs: | • Power supply (green) / Data (yellow) / Status (red) |
| Operating voltage: | • 12-30 VDC, other voltages on request |
| Power consumption: | • 5 Watts, 200 mA (24V) |
| Potentional separation: | • 500 VDC (24 VDC → RS232) |
| Operating temperature: |
• -40°C - +70°C (Multimode and Singlemode with ST or SC) -20°C - +55°C (all others) |
| Storage temperature: | • -40°C - +85°C |
| EMC: | • EN61000-6-2 / EN55022 +A1 + A2 Class B |
| Failure relay: | • 25VDC (1A) /60VDC (0,3A) |
| Weight: | • 500 g |
| Dimensions H x W x D: | • H: 115mm W: 61mm D: 113mm |
| Housing: | • Stainless steel, powder coated |
| Options: | • Fiber View |
| Order No.: | • 01000 21 |