The D1-60A-V is a module suited for DIN rail mounting that can be linked to a local operator panel (F1-10); it provides 6 input channels for reading 0-5 V signals; the double ramp conversion circuit ensures a reliable reading with a 16 bit resolution and a 0.05 % full scale accuracy; the module does not require calibration and mantains its characteristics of accuracy; analog inputs, power section and communication interface are optically isolated; 12 optically isolated digital outputs can be confi gured as alarm units with/without hysteresis; an internal watch-dog circuit ensures a non-stop operation; a RS422/485 serial interface with Modbus (ASCII or RTU) protocol is also available.

General specifications
Power supply: • From 9 to 36V DC, 100mA @24V DC (without F1-10), 170mA (with)
Power supply protections: • Against surge, voltage peaks and polarity inversion
Operating environment: • Temperature: from 0 to +70°C, RH: from 25 to 85% non condensing 
Operating atmosphere: • Without corrosive gas
Storage temperatur: • From -20 to +80°C (without ice)
Electromagnetic compatibility: • Radio frequency emissions: EN55011 group 1 class A
• Conducted emissions: EN55011 group 1 class A
• Radio frequency immunity: ENV50140 10V/m AM from 80 to 100MHz
• Conducted immunity: ENV50141 10V/m AM from 0.15 to 80MHz
IP grade: • Connectors: IP20, enclosure: IP20
Isolation: • Between analog inputs and digital inputs/outputs: 500V
• Between analog inputs and power supply section: 500V
• Between analog inputs and RS422/485 section: 1000V
• Between digital inputs/outputs and RS422/485 section: 1500V
• Between power supply and RS422/485 section: 1500V
LED indication: • Power on, self-test, digital inputs and outputs, serial Rx and Tx
Mounting: • DIN EN50022 rail
Dimensions: • 175 (L) x 120 (H) x 65(D) mm
Weight: • 450g
Ordering code: • R1-120A-V
Analog input specifications
Sensor type: • 6 Voltage sensors (from 0 to 5V)
Analog/digital conversion: • Double ramp, 16 bit resolution
Voltage allowed: • From -1 to 6V
Overall accuracy: • ±5mV
Acquisition rate: • 1s (all six channels)
Full scale temperature range: • 
Cold junction compensation: • 
Digital inputs specifications
Input type: • 2 Inputs, opto-isolated, common positive (power supply voltage)
Voltage levels: • Active state from: 15 to 36V, non active from: 0 to 4V
Current sinked: • 10mA @24V
Detectable pulse duration: • Not less than 500ms
Digital outputs specifications
Output type: • 12 Outputs PNP transistor open collector, pull down resistor: 22kOhm to ground
Output voltage when active: • The voltage supply
Maximum load current: • 100mA each output
Protections: • Suppression diode, overvoltages and short circuit
Communication interface specifications
Communication interface: • EIA RS485 or RS422 (selectable by dip-switch)
Communication speed: • 9600 or 19200 baud (selectable by dip-switch)
Communication protocol: • Modbus ASCII or Modbus RTU (selectable by dip-switch)
Device address: • From 1 to 63 (selectable by dip-switch)
485/422 Lines protections: • Agains surge, short circuits and voltage peaks
Pull-up and pull-down resistors: • 10kOhm
Functional specifications
Watch-dog: • Hardware
RAM data retention: • 
Read software filter: • Movig average, 8 samples depth (individully selectable for each channel)
Input liniarization: • Individually configurable for each channel
Intercepting mode: • Levels mode or hysteresis mode with programmable levels
Input/output links: • Individually configurable
Retaining alarms: • Individually configurable
Retaining alarms reset mode: • All alarms reset by using one of the digital inputs, individually reset by using F1-10 operator panel
Outputs: • With activation and deactivation time filters