BIALON DK-01 PLT

I/O Module with Built-in Room Control for LONWORKS® Power Line Networks

The BIALON DK01 allows control functionality in a LONWORKS® Power Line or Free-Topology network.
Via the STV bus, additional sensors and actuators can be connected and integrated into the LONWORKS® network cost-effectively. All digital inputs and outputs, as well as the sensors and actuators connected to the STV bus, are available for the entire LONWORKS® network as SNVT.

The BIALON DK01 allows control functionality in a LONWORKS® Power Line or Free-Topology network.
Via the STV bus, additional sensors and actuators can be connected and integrated into the LONWORKS® network cost-effectively. All digital inputs and outputs, as well as the sensors and actuators connected to the STV bus, are available for the entire LONWORKS® network as SNVT.
In addition to the digital I/O functions, there is a room control already completely integrated in the BIALON DK01. The room controlling objects in the module are pre-configured already, thus the controller application can be used without extra bindings.
All software objects are programmed according to LONMARK® standard. For the configuration of the
BIALON DK01, there is a free-of-charge LNS plug-in available at the STV web site.

Supply voltage: • 110V to 250V A/C
• 160V to 400V D/C
• 24V AC/DC
Input: • 2x galvanically isolated 12 ... 24V AC/DC,high level > 8 V,
input resistance 4.7kOhm
•  2x galvanically isolated 110 V ... 230V AC/DC, high level > 100 V
input resistance 220 kOhm
Relay outputs: • 2x galvanically isolated, switching voltage max. 230V AC/DC,
16A ohm resistive load; 8A inductive load (cos ϕ = 0.5), turnkey
Serial interface: • 2400 Baud (STV bus)
Micropocessor: • Neuron® 3150
Indication: • Green LED: 2x LED 2x digital input
• Yellow LED: 2x LED 2x digital output
• Green LED: Power On
• Yellow LED: service; fault
• Green LED: PKD (Packed Detect)
• Yellow LED: BIU (Band In Use)
Installation: • service pin
Transmission media: • LON Power Line
• LON Power Line currentless (max. 20,000m)
• FTT-10A
Operating temperature: • 0 ... 50°C
Relative Humidity: • 0 ... 90% (not condensing)
Housing: • According to EN 50022 for DIN rail mounting,
6 separating units, protection class IP 20
Dimensions (LxWxH) • 108 mm/90 mm/66 mm (6 SU; DIN rail 50022)
ordering number: • 98F3200

• Room control