Analog and/or digital to SM fiber optic converter, IOL3000-ST
The IOL3000 units are able to transmit up to 8 digital signals (12–24 VDC) and/or 4 analog signals (0–10 V or 0–20 mA, digitalized via an A/D converter with a resolution of 10 Bit within a point-to-point structure or line-structure via Singlemode fiber optic witrh a ST connectotr. The receiver moduls comes in two versions, with relay (IR added on the article code) or with a transistor outputs.
Product variants
Article Number | Product Name | |
---|---|---|
030001131 and 030002131 + | IOL-3000/TX-4A-V-13-SM-ST Transmitter + Receiver/24V/4xA/SM/ST | + Request quote |
IOL3000, 4x analog 0-10V, Transmitter + Receiver, ST, via singlemode fiber optic | ||
030001231 and 030002231 + | IOL-3000/8D4A-V-13-SM-ST Transmitter + Receiver/24V/8xD/4A/SM/ST | + Request quote |
IOL3000, 8x digital + 4x analog 0-10V, Transmitter + Receiver, ST, via singlemode fiber optic | ||
030001331 and 030002331 (IR) + | IOL-3000/8D-13-SM-ST Transmitter + Receiver/24V/8xD/TX/SM/ST | + Request quote |
IOL3000, 8x digital, Transmitter + Receiver, ST, via singlemode fiber optic | ||
030001431 and 030002431 + | IOL-3000/8D4A-A-13-SM-SC Transmitter + Receiver/24V/8xD/4A/SM/ST | + Request quote |
IOL3000, 8x digital + 4x analog 0-20mA, Transmitter + Receiver, ST, via singlemode fiber optic | ||
030001531 and 030002531 + | IOL-3000/TX-4A-A-13-SM-ST Transmitter + Receiver/24V/4xA/SM/ST | + Request quote |
IOL3000, 4x analog 0-20mA, Transmitter + Receiver, ST, via singlemode fiber optic |
Description
The fiber optic system IOL3000 transmits digital signals (e.g., contact closures, control-signals) and analog signals via fiber optics.
The fiber optic system is able to transmit up to 8 digital signals (12–24 VDC) and/or 4 analog signals (0–10 V or 0–20 mA, digitalized via A/D converter with a resolution of 10 Bit) within a point-to-point structure or line-structure.
The interconnection of an input/pass system (ED) allows the transmission of additional digital and analog data. You can choose if you want to have an electric disjunction (OR) of electrically and optically received data or if the electric data shall overwrite the optical data. In case of analog data the DIP switch must be used to decide whether the optical or the electrical signals shall be transmitted. The devices are available for line or ring structures as one fiber solutions.
LEDs and potential-free contacts of a fault detector relay are able to signal defective states.
Specifications
- FO-connector:
- ST
- Fiber type:
- Singlemode 9/125μm
- Optical budget:
- 16 dB
- FO range:
- 30 km, others up to 100 km on request (0,3 dB/km)
- Wavelength:
- 1310 nm (1310/1550 nm for BIDI version)
- Accuracy receiver:
- 0,2%
- Cable lenght:
- 1m
- Connector:
- 16-pole terminal
- Status-LEDs:
- Power supply (green) / Data (yellow) / Status (red)
- Power supply:
- 12 - 30 VDC, other voltages on request
- Power consumption:
- 5 Watts, 200 mA (24 V)
- Galvanic isolation:
- 500VDC
- Operating temperature:
- -40°C to +70°C (Multimode and Singlemode with ST or SC) / -20°C to +55°C (all others)
- EMC:
- EN61000-6-2/EN55022 Class B + A1 + A2
- Weight:
- 570 g
- Dimensions:
- 60 x 100 x 113 mm (60 x 120 x 113 mm incl. connector)
- Housing
- Stainless steel, powder coated