0401-DAT5023Iac/A

High AC/DC-current to current or voltage signal converters, DAT5023/I

The converter DAT 5023Iac is designed to detect the TRMS value of the AC current signal from 0÷5 A to 0÷60 A applied on its input providing a voltage or current output signal. The user can program the input and output ranges by the proper DIP-switches available after opening the suitable door located on the side of device. The regulation of Zero and Span values is made by the ZERO and SPAN potentiometers located on the top of device. The 2000 Vac isolation between power supply and output eliminates the effects of all ground loops eventually existing and allows the use of the converter in heavy environmental conditions found in industrial applications. The measure of the input signal is executed by a cross connector and a Hall effect transducer; this allows to isolate the input side from the output and power supply.

Read more

Product variants

Article Number Product Name
0401-DAT5023Iac/A + DAT5023Iac/A + Request quote
input AC high current min. 0 ÷ 5A max. 0 ÷ 10A, output 0/4-20mA or 0-10V
0401-DAT5023Iac/B + DAT5023Iac/B + Request quote
input AC high current min. 0 ÷ 20A max. 0 ÷ 30A, output 0/4-20mA or 0-10V
0401-DAT5023Iac/D + DAT5023Iac/D + Request quote
input AC high current min. 0 ÷ 40A max. 0 ÷ 60A, output 0/4-20mA or 0-10V
0401-DAT5023Idc + DAT5023Idc + Request quote
input DC high current min. 0 ÷ 5A max. 0 ÷ 60A, output 0/4-20mA or 0-10V

Description

The converter DAT 5023Iac is designed to detect the TRMS value of the AC current signal from 0÷5 A to 0÷60 A applied on its input providing a voltage or current output signal. The user can program the input and output ranges by the proper DIP-switches available after opening the suitable door located on the side of device. The regulation of Zero and Span values is made by the ZERO and SPAN potentiometers located on the top of device. The 2000 Vac isolation between power supply and output eliminates the effects of all ground loops eventually existing and allows the use of the converter in heavy environmental conditions found in industrial applications. The measure of the input signal is executed by a cross connector and a Hall effect transducer; this allows to isolate the input side from the output and power supply.

FEATURES
- Input for AC current signal
- Build-in cross connector (8mm diameter)
- Measure by Hall effect transducer
- True Root Mean Square (TRMS) measure
- Galvanic isolation at 2000 Vac
- Isolated power supply source for passive loads on output
- Independent zero and full scale regulations
- EMC compliant – CE mark
- DIN rail mounting in compliance with
 - EN-50022 and EN-50035

Specifications

Power supply:
  • Voltage | 18 - 30VDC
  • Rever. polarity protection | 60VDC max
  • Aux. Power supply OUT | 12VDC min@20mA
Current consumption:
  • With active power supply | 90mA max.
  • Voltage output | 60mA max.
Isolation:
All the ways | 2000VAC, 50Hz, 1min
Temperature & humidity:
  • Operation | -20°C to +60°C
  • Storage | -40°C to 85°C
  • Humidity non condensing | 0 to 90%
EMC (for industrial environment):
  • Directive | 2004/108/EC
  • Imunity | EN 61000-6-2
  • Emission | EN61000-6-4
Input:
  • DAT5023Iac/A | min. 0 ÷ 5A, max. 0 ÷ 10A
  • DAT50223iac/B | min. 0 ÷ 20A, max. 0 ÷ 30A
  • DAT50223iac/D | min. 0 ÷ 40A, max. 0 ÷ 60A
  • DAT5022Idc | min. 0 ÷ 5A, max. 0 ÷ 60A
Bandwidth:
40Hz ÷ 1KHz
Input calibration:
±0.1% f.s.
Linearity:
  • 1% f.s.
  • DC | 0.1% f.s.
Thermal drift:
Full scale | ± 0.02%/°C
Output:
  • Current | 0mA to 20mA or 4mA to 20mA
  • Voltage | 0V oto 10V, 2V to 10V, 0V to 5V or 1V to 5V
Load resistance:
  • Voltage output | >/=5K Ohm
  • Current output | </=500 Ohm
Responce time (10÷90% of f.s.):
About 400ms
Housing:
  • Material | Self-extinguishing plastic
  • Dimensions | WxLxH 90x112x12.5mm
  • Weight | 90g

Do you have a request?

Request type
Art. Nr. Product name Remove

You can add another variation to your request

Do you have a request?