Modbus data acquisition I/O, D1-40A-x
The D1-40A-V and D1-40A-I Modbus data acquisitions modules are available with 6x 0-5VDC or 6x 4-20mA inputs. An A/D converter with 16 bit resolution is used for the analog to digital conversion. The modules have a RS485 or RS422 interface and the communication protocol is Modbus ASCII or RTU and can be mounted on a DIN-rail.
Product variants
Article Number | Product Name | |
---|---|---|
425042.1 + | D1-40A-V | + Request quote |
Analog isolated module with 6 common ground input channels (0-5V) | ||
425041.1 + | D1-40A-I | + Request quote |
Analog isolated module with 6 common ground input channels (4-20mA) |
Description
The D1-40A-V module provides 6 input channels for reading of 0-5 V analog signals; the double ramp conversion circuit ensures a reliable reading with a 16 bit resolution and a 0.05 % full scale accuracy; the module does not require calibration and mantains its characteristics of accuracy; analog inputs, power section and communication interface are optically isolated; an internal watch-dog circuit ensures a non-stop operation; interface type (RS422 or RS485), communication protocol (Modbus ASCII or RTU) and address (from 1 to 63) can be set through microswitches; the module is suited for mounting on a DIN rail.
The D1-40A-I module provides 6 input channels for reading of 0/4-20 mA analog signals; the double ramp conversion circuit ensures a reliable reading with a 16 bit resolution and a 0.05 % full scale accuracy; the module does not require calibration and mantains its characteristics of accuracy; analog inputs, power section and communication interface are optically isolated; an internal watch-dog circuit ensures a non-stop operation; interface type (RS422 or RS485), communication protocol (Modbus ASCII or RTU) and address (from 1 to 63) can be set through microswitches; the module is suited for mounting on a DIN rail.
Specifications
- Sensor type:
-
- 6x voltage sensors 0-5V
- 6x current sensors 0-20mA
- Power supply for external sensors:
- 24VDC, max. current 100mA
- Analog to digital conversion:
- 16 bit resolution
- Voltage/current allowed:
-
- -1 to +6VDC
- 0 to +25mA
- Input impedance:
-
- Voltage: 20 kOhm
- Current: 246 Ohm
- Current- 45mA
- Overall accuracy:
-
- Voltage: ± 5mV
- Current: ± 10µA
- Acquisition rate:
- 1 sec. for all the channels
- Communication interface:
- RS485 or RS422 (selectable by jumper)
- Communication speed:
- 9600 or 19200 baud
- Communication protocol:
- Modbus ASCII or Modbus RTU
- Device address:
- 1 to 63 selectable by dip-switches
- RS485/RS422 line protection:
- Against surge, short circuits and voltage peaks
- Pull-up and pull-down resistors:
- 10 kOhm
- Watch-dog:
- Yes
- Power supply:
- 9 to 36VDC, 100mA @ 24VDC
- Operating temperature:
- 0°C tot +70°C, relative humidity: 25 to 85% non condensing
- Storage temperature:
- -20°C tot +80°C
- Mounting:
- DIN-rail
- Dimensions:
- LxHxD 175 x 120 x 65mm
- Weight:
- 360g