ZigBee single phase energy meter, ZR-HM.D-M
ZigBee single phase energy meter up to 15kW.
Product variants
Article Number | Product Name | |
---|---|---|
0414-ZR-HM.D-M + | ZR-HM.D-M | + Request quote |
ZigBee single phase energy meter up to 15kW | ||
0414-ZR-HM.W-M + | ZR-HM.W-M | + Request quote |
ZigBee single phase energy meter up to 15kW, wall mount |
Description
The ZR-HMD-M Energy Meter includes an external 70Amp current transformer to measure real time power up to 15kW and has an energy counter.
Moreover it has a digital output to drive high power relay. Functions as stand-by killer and override push button are also available. It is possible to set a power limit below of which the load is considered in stand-by mode and therefore the external relay is switched off. With the override push-button the user can override the last relay order issues by the Gateway. All the function are activated by simple ModBus commands issued to the ZB-Connection Gateway that transforms those commands in wireless commands.
The device is continuously powered by 230 Vac; therefore it can also act as a repeater or a “parent” device for battery-powered sensors.
Key features:
- Real Time Electricity Active Power Measurement up to 15 kW with external CT included
- Electricity Energy Counter
- Digital output to drive external high power relay
- Stand-by killer
- Override push-button
- CT included with core split
- Din Rail Mounted
- Modbus profile on ZigBee platform
- Router function
Specifications
- General specifications:
-
- Chip Ember EM250
- Compatible IEEE 802.15.4
- Stack EmberZnet 3.5.x (ZigBee PRO)
- Modbus/RTU
- Address settable through radio command
- RF characteristics:
-
- Frequency: 2405 MHz ÷ 2480 MHz
- Modulation: DSSS
- Nominal transmission power: 2mW (3 dBm)
- Receiver sensitive: -95 dBm
- Internal antenna gain: 0 dB
- Outdoor/indoor range: 100m/30m
- Power supply:
- 90/250 Vca; 1W; 50/60Hz
- Measurement:
-
- Active Power [W]
- Energy consumption [Wh]
- CT:
- 70A max.
- Digital output:
- For auxiliary relay 230 Vac, 40mA max.
- Connections:
- Terminal blocks (5,08 mm pitch)
- Environment Parameters:
-
- Operating temperature: -10 ÷ +60°C; <80% U.R. not condensing
- Storage temperature: -20 ÷ +70°C; <80% U.R. not condensing
- Conformity:
-
- Community Directives 2006/95/EEC, 89/336/EEC, 99/5/EEC
- ETSI-EN 300 328; ETSI EN301 489; EN 50371
- EN60950-1; EN61000-6-2; EN61000-6-3