0414-ZR-HM.D-M

ZigBee single phase energy meter, ZR-HM.D-M

Product group

ZigBee single phase energy meter up to 15kW.

Read more

Product variants

Article Number Product Name
0414-ZR-HM.D-M + ZR-HM.D-M + Request quote
ZigBee single phase energy meter up to 15kW
0414-ZR-HM.W-M + ZR-HM.W-M + Request quote
ZigBee single phase energy meter up to 15kW, wall mount

Description

The ZR-HMD-M Energy Meter includes an external 70Amp current transformer to measure real time power up to 15kW and has an energy counter.
Moreover it has a digital output to drive high power relay. Functions as  stand-by killer and override push button are also available. It is possible to set a power limit below of which the load is considered in stand-by mode and therefore the external relay is switched off. With the override push-button the user can override the last relay order issues by the Gateway. All the function are activated by simple ModBus commands issued to the ZB-Connection Gateway that transforms those commands in wireless commands.
The device is continuously powered by 230 Vac; therefore it can also act as a repeater or a “parent” device for battery-powered sensors.

Key features:

  • Real Time Electricity Active Power Measurement up to 15 kW with external CT included
  • Electricity Energy Counter
  • Digital output to drive external high power relay
  • Stand-by killer
  • Override push-button
  • CT included with core split
  • Din Rail Mounted
  • Modbus profile on ZigBee platform
  • Router function

Specifications

General specifications:
  • Chip Ember EM250
  • Compatible IEEE 802.15.4
  • Stack EmberZnet 3.5.x (ZigBee PRO)
  • Modbus/RTU
  • Address settable through radio command
RF characteristics:
  • Frequency: 2405 MHz ÷ 2480 MHz
  • Modulation: DSSS
  • Nominal transmission power: 2mW (3 dBm)
  • Receiver sensitive: -95 dBm
  • Internal antenna gain: 0 dB
  • Outdoor/indoor range: 100m/30m
Power supply:
90/250 Vca; 1W; 50/60Hz
Measurement:
  • Active Power [W]
  • Energy consumption [Wh]
CT:
70A max.
Digital output:
For auxiliary relay 230 Vac, 40mA max.
Connections:
Terminal blocks (5,08 mm pitch)
Environment Parameters:
  • Operating temperature: -10 ÷ +60°C; <80% U.R. not condensing
  • Storage temperature: -20 ÷ +70°C; <80% U.R. not condensing
Conformity:
  • Community Directives 2006/95/EEC, 89/336/EEC, 99/5/EEC
  • ETSI-EN 300 328; ETSI EN301 489; EN 50371
  • EN60950-1; EN61000-6-2; EN61000-6-3