M-Bus naar IP interface omvormer, MPW120/IP
BESD biedt een breed scala aan M-bus naar IP-interfaceconverters voor 120 apparaten met een M-bus-interface. Er zijn verschillende converters met een Ethernet naar M-Bus interface. De modules, geschikt voor DIN-rail montage, kunnen worden geleverd met een 24V AC/DC of 230V AC voeding aansluiting.
Product varianten
Artikelnummer | Productnaam | |
---|---|---|
095170 + | BIALON MPW-120/IP 230Vac | + Vraag offerte aan |
M-Bus level converter for 120 M-Bus devices, 10/100MBaseT Ethernet interface, power supply 230VAC | ||
095171 + | BIALON MPW-120/IP 24Vac/dc | + Vraag offerte aan |
M-Bus level converter for 120 M-Bus devices, 10/100MBaseT Ethernet interface, power supply 24V AC/DC |
Beschrijving
The M-Bus level converter BIALON MPW-120/IP lets you connect up to 120 M-Bus endpoints with a standard load of 1.5 mA each to an M-Bus Master via an Ethernet connection.
The M-Bus Master can be, e.g., a PC or an embedded controller. The level converter translates the signals from the M-Bus Master on the Ethernet interface to M-Bus signals.
Up to 250 MPW-60/IP can be connected to a PC-based M-Bus Master. The IP addresses on the level converter are assigned to virtual COM ports on the master. If needed, they can be grouped on the M-Bus Master via an additional program to use a single COM port. This means that an M-Bus Master program that only works with one COM port can communicate simultaneously with all M-Bus endpoints connected via the individual level converters.
The level converter has overload protection and is thus short-circuit protected. The trip threshold is 200 mA. Additionally, the M-Bus interface has overvoltage protection on the bus side.
The LEDs indicate the major operational and malfunction states, such as power supply, send or receive data, and bus overload.
The M-Bus BIALON MPW-120/IP level converter is available in two variants either with a 230 V AC or 24 V AC/DC power supply.
Specificaties
- M-Bus endpoints:
- 120 (standard load: 1.5 mA)
- Supply voltage:
- 110 V to 250 V AC or 20 V to 28 V AC/DC
- M-Bus voltage:
- 36 V - 42 V
- max. M-Bus idle current:
- 180 mA (120 standard loads)
- Over cuurent threshold:
- <200 mA
- Electrical isolation:
- between the power supply, Ethernet and M-Bus
- Ethernet:
- 10/100BaseT
- Transfer rate:
- M-Bus 300 … 9600 baud
- LED indication:
-
- LED green: power on
- LED yellow: Transmit M-Bus
- LED green: Receive M-Bus
- LED red: Bus Overload
- LED green: PKD (Packet Detect –> IP port)
- LED yellow: LNK (Link Status –> IP port)