M-Bus interface omvormer, MPW-6
Met de M-Bus signaal omvormer MPW-6, kunnen tot 6 M-Bus apparaten (elk met een standaard load van 1.5 mA) worden verbonden met een M-bus master via een RS232 of RS485 verbinding. De M-bus master kan een PC of een embedded controller zijn met een RS232 of RS485 interface.
Product varianten
Artikelnummer | Productnaam | |
---|---|---|
095074 + | MPW6 24VAC/DC - RS232 | + Vraag offerte aan |
M-Bus level converter for 6 M-Bus devices, RS232 interface, power supply 24V ac/dc | ||
095073 + | MPW6 24VAC/DC - RS485 | + Vraag offerte aan |
M-Bus level converter for 6 M-Bus devices, RS485 interface, power supply 24V ac/dc |
Beschrijving
With the M-bus level converter MPW-6, you can connect up to 6 M-bus-terminals (with a M-bus
standard load of 1,5 mA each) to an M-bus-master via RS-232 connection or a RS-485 interface. The Mbus-
master can be e.g. a PC or an embedded controller. The level converter thereby converts the coming
signals from the M-bus-master via the RS-232 or RS-485 interface into M-bus signals.
The level converter owns an overload protection and is short circuit proof. The overcurrent response
threshold is 30 mA. Furthermore, the M-bus interface of the level converter bus-side has an overvoltage
protection.
The 3 LEDs inform about the substantial operating and error conditions. Voltage supply is indicated by the
green power LED. Sending or receiving data is indicated by a two-color LED green/yellow. Additionally,
the level converter has a red bus-overload-LED indicating excess of the M-bus amperage.
The M-bus level converter MPW-6 is available in two variants, namely with RS-232 or RS485
interface.
Specificaties
- Supply voltage:
- 24VAC/DC
- M-Bus voltage:
- 30V
- max. M-Bus idle current:
- 9 mA (6 standard loads)
- Over cuurent threshold:
- < 30mA
- Electrical isolation:
- between RS232/RS485 and M-Bus
- Transfer rate:
- 300 - 38400 baud
- LED indication:
-
- LED green/yellow: Transmit/ Receive M-Bus
- LED green: power
- LED red: Bus overload
- M-Bus connection:
- Terminal pairs max. 2.5 mm²
- RS232/RS485 connection:
- 3 terminals max. 2.5 mm² TD RD GND (RxD from PC) (TxD from PC) (GND from PC)
- 24 V AC/DC connection:
- 3 terminals max. 2.5 mm²
- Operating temperature:
- 0 to 50°C
- Relative humidity:
- 0 to 90 % (non-condensing)
- Housing:
- In accordance with EN 50022 for installation on DIN-rails, 2 TE units
- Degree of protection:
- IP 20
- Dimensions (L x W x H):